PWS7062R5 Air/ water heat exchanger

This range of vertical air-water heat exchanger, PWS, with a IP 55 protection degree, is ideal for dusty environments with high temperatures. Air cleanliness and the temperature around the enclosure will not affect the heat exchanger's performance. Several sizes of the heat exchanger are available, making the choice of the most optimum heat exchanger easy.

GOST
Feature: IP 55
PWS2
Characteristics  
Height 500 mm
Width 200 mm
Depth 100 mm
Cooling Capacity 200 l/h - W10/A35 (W) 600
Power W10/A35 (W) 68 / 70
Current W10/A35 (A) 0.35 / 0.38
Pre fuse T (A) 4
Starting current W10/A35 (A) 1.50 / 1.80
Unimpeded airflow (m³/h) 440
Noise (dB) ≤48
Frequency (Hz) 50 / 60
Weight (kg) 6.65
Operating voltage 230V 50/60Hz
PWS Product ImagePWS Catalogue drawing image
Item no.: PWS7062R5
EAN no.: 8713574130968
  • Technical data
  • Features
  • Downloads
  • Certificates

Technical data

Description:

For vertical installation. Additional work is not required to the cutout to guarantee the IP. Integrated thermostat and solenoid valve for temperature control, and temperature monitoring with alarm contact. The thermostat is adjustable between 8 °C and 50 °C, factory setting 35 °C. Maximum permissible operating pressure of 10 bar. The cooling capacity for specific conditions are indicated in the diagrams. Water inlet temperature between 1 °C up to 35 °C.

Type of connection:

Spring-type terminal included with plug for electrical connection, 13 mm hose nozzle for water pipe connections.

Material:

Housing made of galvanized steel powder coated. Heat exchanger made of copper pipe with aluminium fins.

Ambient temperature range:

+1 °C to +70 °C.

Protection:

IP 55 towards the electrical enclosure.

Finish:

RAL 7035.

Approvals:

CE, GOST.

Pack quantity:

One unit.

Features

Feature:

Vertical Air-Water heat exchanger with a IP 55 protection degree.

Advantage:

The heat exchanger provides ventilation without using the air immediately around the enclosure. Customers can choose the heat exchanger that meets their requirements the most, removing any extra costs due to oversizing.

Benefit:

The air cleanliness and temperature immediately around the enclosure will not affect the performance of the heat exchanger, making it a good solution for dusty environments with high temperatures.

CAD 2D drawing (DXF) PWS7062R5 1 MB
CAD 2D drawing (PDF) PWS7062R5 91 KB
CAD 3D drawing (STEP) PWS7062R5 6 MB
CAD drawing (EMA) PWS7062R5 EPLAN 148 KB
Image (JPG 591 x 800 px) PWS Catalogue drawing image 125 KB
Image (JPG 600 x 600 px) PWS Product Image 60 KB
Image (JPG 404 x 472 px) PWS2 46 KB
Item sheet (PDF) PWS7062R5 ENGLISH 103 KB
Manual (PDF) PWS-PWD Manual 153 KB
Mounting instructions document (PDF) Thermal Management PWS 365 KB
Document (PDF) GOST 497 KB