G280416G051 Spectra Indoor-SS 1000W, 115V

SpectraCool Indoor/Outdoor G-Series SS in stainless steel, with IP56 protection degree is designed for rugged factories, where an indoor stainless steel AC with high IP is needed. The unit comes with dust resistant condenser coils and is equipped with flanges for simple installation on to the enclosure.

CE Declaration of Conformity Declaration of Compliance EAC cULus_UL Listed
Feature: IP56 TYPE 4X
SpectraCool Indoor-Outdoor G-Series SS Product Image
Characteristics  
Height 726.2 mm
Width 432.1 mm
Depth 284.0 mm
Cooling capacity L35L35 (W) 967/1000
Power supply (V/ph/Hz) 115 / 1 / 50-60
Max. Nominal current (A) 10,4/10,1
Starting current (A) 36,2
Noise level (dB) 68
Weight (kg) 38.00
Cooling capacity L55/L55 (W) 1084
Max power consumption (W at 50/60Hz) 465/1055
Item no.: G280416G051
EAN no.: 8713574238039
  • Technical data
  • Features
  • Downloads
  • Certificates

Technical data

Description:

SpectraCool Indoor G-Series in stainless steel is the air conditioning solution for rugged factory environments. Units have an active condensate management. Cleanable, reusable aluminium mesh filter protects coils for maximum cooling performance. The mechanical thermostat is inside the unit. The factory setting is 27 °C.

Type of connection:

Terminal block.

Material:

Stainless steel type 304.

Temperature limits inside:

+22 °C ... +45 °C.

Temperature limits outside:

Indoor model, +10 °C … +55 °C; Outdoor model, -40 °C … +55 °C.

Protection:

IP56 | TYPE 4X.

Finish:

Brushed stainless steel.

Features

Feature:

Vertical AC units that can be used in rugged indoor environments, with IP56 protection degree.

Advantage:

A unit that best meets cooling requirements can be easily selected, eliminating any extra costs due to oversizing.

Benefit:

Easy-mount flanges for simple installation. The units is shipped with an inlet air filter. R404c and R134a earth friendly refrigerants are used.

Comment:

To minimise energy consumption of the cooling unit, it is recommended to install a door switch, DSW01. The door switch will turn the cooling unit off when the door is opened.

Dxf (DXF) G28_115V4000BTU 636 KB
Dxf (DXF) G28_115V4000BTU_PartialRecess 596 KB
Image (JPG 600 x 800 px) SpectraCool Indoor-Outdoor G-Series SS Product Image 27 KB
Item sheet (PDF) G280416G051 ENGLISH 196 KB
Mounting instructions document (PDF) SpectraCool Indoor-Outdoor G-Series SS - G28 3 MB
Mounting instructions document (PDF) SpectraCool Indoor-Outdoor G-Series SS - G52 2 MB
Mounting instructions document (PDF) SpectraCool Indoor-Outdoor G-Series SS - G57 3 MB
Product sheet (PDF) SpectraCool Indoor/Outdoor G-Series SS 2 MB
Product sheet (PDF) SpectraCool Indoor/Outdoor G-Series SS(RUSSIAN) 102 KB
Step (STEP) G28_115V4000BTU 20 MB
Step (STEP) G28_115V4000BTU_PartialRecess 20 MB
Document (PDF) CE Declaration of Conformity 87 KB
Document (PDF) Declaration of Compliance 77 KB
Document (PDF) EAC 2 MB
Document (PDF) cULus_UL Listed 432 KB