ECHT150 Heater 150W

This double insulated compact heater, ECH(T) is available with or without a thermostat. Water condensation is eliminated, also when the ambient temperature drops sharply. Choosing a version with an already integrated thermostat will save space inside the enclosure and reduce installation time compared with a thermostat mounted separately.

Feature: IP 20/II
ECH(T) Product Image
Characteristics  
Heating Capacity (W) 150
Starting current (A) 8.0
L (mm) 150
Voltage (V) 120-240 V AC
Weight (kg) 0.50
ECH(T) Catalogue drawing image
Item no.: ECHT150
EAN no.: 8713574121768
  • Technical data
  • Features
  • Downloads

Technical data

Description:

Double insulated vertical heater to prevent condensation. Mounting clip for 35 mm DIN rail (EN60715). Touch-safe heater, the temperatures of the housing are kept under 80ºC except upper protective grille. The heater with thermostat (ECHT) includes a plug-in thermostat therefore it does not require additional wiring, starting temperature of 5ºC, and switch-off temperature of 15ºC.

Heating element:

PTC resistor, temperature limiting,

Material:

Plastic according to UL94 V-0

Operating temperature:

-45°C to +70°C. The heating capacity is for ambient temperature 20ºC.

Connection:

Pole terminal 2.5 mm², torque 0.8Nm max.

Protection:

IP 20, Class II (double insulated).

Approvals:

CE, EAC.

Finish:

Black,

Pack quantity:

1 piece.

Features

Feature:

Double insulated compact heater, with or without a thermostat.

Advantage:

The housing of the heater is kept under 80°C due to the heaters double insulation. For the heater with an integrated thermostat, customers save installation time as the thermostat does not need to be connected.

Benefit:

When installed, water condensation will be avoided especially in situations when the ambient temperature dramatically drops. For the heater with an integrated thermostat, customer's labour costs are reduced due to not having to install a separate thermostat, which also saves space inside the enclosure.

Comment:

A thermostat with a normally closed contact, ETR or EFR, is recommended in order to control the heater.

CAD 2D drawing (DXF) ECHT150 111 KB
CAD 2D drawing (PDF) ECHT150 77 KB
CAD 3D drawing (STEP) ECHT150 781 KB
Image (JPG 800 x 344 px) ECH(T) Catalogue drawing image 58 KB
Image (JPG 600 x 600 px) ECH(T) Product Image 62 KB
Item sheet (PDF) ECHT150 ENGLISH 61 KB